Power SolutionsMPower SolutionsLIBERTY®SERIES 1000 FRONT ACCESS MONOBLOCKVALVE-REGULATED (SEALED)LEAD ACID BATTERIESINSTALLATION AND OPERATING INSTRUC
8SECTION 3 - INSTALLATION AND ASSEMBLY1.3.1 InstallationLiberty®Series 1000 FAM and FA batteries are best installed horizontal-ly. Physical dimensions
Model FAM 12-100 FA 12-125* FAM 12-150Nominal 12 volts 12 volts 12 voltsvoltageNumber 6 / Unit 6 / Unit 6 / Unitof cellsRated 8-hrcapacity(ampere- hou
FV/Time Models 1 hr. 3 hr. 5 hr. 8 hr. 10 hr. 20 hr.FAM 12-100 66.3 28.1 18.5 12.4 10.2 5.51.75 FA 12-125 86.3 37.1 24 15.8 12.9 6.8FAM 12-150 99.9 43
111.3.2 Connecting and torquing battery terminal postsFAM and FA batteries are available in three 12 volt modules sizeswith the following ampere - ho
PART 2CHARGING and OPERATION OF BATTERYSECTION 1 - CHARGINGCAUTIONAlways recharge a battery immediately after a discharge to avoid degradation of the
Higher than normal storage temperature (77°F [25°C] nominal) will acceler-ate internal self-discharge of a battery by a factor of two for each 15°F (9
142.1.4 Initial charge recordsAt the completion of the initial charge and after the cells have been onfloat charge for approximately one week, record
15An equalizing charge can be provided when individual cell voltages go below the minimum value shown in Table 3 or 0.05 Volts below the float voltage
TABLE 3CHARGE VOLTAGES FORLIBERTY SERIES 1000 FRONT ACCESS CELLSCHARGE VOLTAGES AT 77°F (25°C)Note 1:1 - Applies to average cell voltage. Battery volt
SECTION 3 - MAINTENANCE OF BATTERY MODULES2.3.1 InspectionLiberty 1000 Series Front access modules are sealed VRLA valve-regulat-ed lead acid batterie
SAFETY PRECAUTIONSOwners are hereby advised that access to this battery should be limited to personnel whohave been trained in the installation, prepa
• Increases internal discharge or local action losses• Lowers cell voltage for a given charge current• Raises charging current for a given charge volt
192.3.7 Internal Ohmic measurementsThere are currently three methods being used today to measure theinternal condition of the battery. Those methods a
14-312 1MATERIAL SAFETY DATA SHEET SECTION I: CHEMICAL PRODUCT AND COMPANY IDENTIFICATION PRODUCT IDENTITY:Sealed, Lead
21 14-312 2handling.SECTION IV: FIRST AID MEASURES EMERGENCY AND FIRST AID PROCEDURES: SKIN / EYES x Flush with water for 15 minutes x Remov
22 14-312 3Boiling Point: N/A Vapor Pressure: N/A Vapor Density: (air=1): >1 Melting Point: N/A Evaporation Rate (water=1): N/A Solubil
23 14-312 4SECTION XV: REGULATORY INFORMATION See 29 CFR 1910.268(b)(2)SECTION XVI: OTHER INFORMATION The information herein is given in good
2414-3321MATERIAL SAFETY DATA SHEET SECTION I: CHEMICAL PRODUCT AND COMPANY IDENTIFICATION PRODUCT IDENTITY:Sealed, Lead-Calcium BatteryCDID:LIBER
2514-3322SECTION IV: FIRST AID MEASURES EMERGENCY AND FIRST AID PROCEDURES: SKIN / EYES x Flush with water for 15 minutes x Remove contaminated cloth
2614-3323Appearance / Odor: colorless, oily fluid, acrid odor when hot. Boiling Point: N/ASECTION X: STABILITY AND REACTIVITY STABILITY: This batt
Appendix B - WARRANTY PROVISIONS FOR LIBERTY®SERIES1000 FAM and LFA BATTERIESC&D TECHNOLOGIES valve-regulated lead acid batteries are warrant-ed a
LIBERTY®SERIES 1000 FRONT ACCESS MONOBLOCKVALVE-REGULATED (SEALED) LEAD ACID BATTERIESINSTALLATION AND OPERATING INSTRUCTIONSTABLE OF CONTENTS PAGEINT
Appendix C - VALVE-REGULATED LEAD ACID BATTERY andCHARGER INSPECTION REPORTA sample inspection report form is provided in the following pages ofthis m
Power SolutionsA Division of C&D Technologies, Inc.A Division of C&D Technologies, Inc.A Division of C&D Technologies, Inc.COMPower Soluti
BATTERY CHARGE STATUS OPEN CIRCUIT FLOAT EQUALIZEBATTERY BUS VOLTAGE __________Vdc __________Vdc _________VdcLocation: Model: Date:Internal C
31
Printed in U.S.A.100/707/WLG/3Power SolutionsA Division of C&D Technologies, Inc.A Division of C&D Technologies, Inc.A Division of C&D Tec
WARNINGThis battery is designed for industrial use only and is not intended for application in vehicular starting, lighting, and ignition and/or opera
3Maintenance1. Digital voltmeter w/ temperature probe.2. Torque wrench.3. Insulated wrenches.4. Resistance, conductance or impedance meter.Warning: Do
INTRODUCTIONThe batteries referenced in this document are sealed lead acid batteriesreferred to as FAM and FA batteries. They are constructed with ana
5RECOMMENDED TECHNICAL REFERENCES AND EXPERTISEThis battery should be installed by a competent professionalwho has been trained in the installation of
6PART 1RECEIVING AND INSTALLATIONSECTION 1 - RECEIVING1.1.1 General Information and PrecautionsThis battery is designed for industrial use only and is
7SECTION 2 - STORAGE1.2.1 Storing Charged BatteriesStore batteries indoors in a cool, dry location between 20°F (-7°C)and 90°F (32°C) and place the b