Cd-technologies RS-2061 Standby Batteries for Renewable Energy App Manuel d'utilisateur Page 11

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 14
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 10
Charging Voltage Temperature Compensation Chart
Electrolyte Freezing
To prevent freezing make be sure maintain a high state of charge and thus a high specific gravity in the bat-
tery. The following graph gives the freezing point of the electrolyte at different specific gravities.
Testing
Batteries are rated on an ampere-hour basis or on their ability to deliver a certain number of amperes to the
load for a specified amount of time before cell voltages drop to a given potential. It is important to realize that
the ampere-hour capacity of a cell or battery depends on the rate at which it is discharged.
The C&D Technologies lead acid battery and cells are designed for optimum discharge characteristics of
long rate discharge. This permits batteries to discharge to lower end-potentials of 1.90 volts per cell. It is
also important to consider low ambient operating temperatures when calculating required battery size.
Low operating temperatures will reduce available battery capacity significantly.
To be valid, a capacity test must assume the following:
• Afullychargedbatteryandbalancedcellpotentials.Insomecases,thismayrequireanequalize
charge or, in cases of sulfation, other action. Consult the C&D Technologies Technical Services
Department.
• Allcellsequalizedtotheirnominalspecificgravity.Thismayrequireadditionorwithdrawalofacid
and should only be done following a complete recharge and equalizing charge.
• Atleast72hoursonnominalsystemvoltage.Thisisespeciallyimportantfollowinganequalizecharge,
to clear excessive gasses developed at the surface of the plates by letting the battery rest off charge or
on float charge.
• Temperaturecorrectionforcellstestedatanytemperatureotherthan77°F(25°C).
• Batteriesarefullychargedandallconnectionsarecorrect.
CPV Models
VR Solar
®
D, K, L - CPS
+ 2.8 mV/F per cell below 77°F (25°C)
- 2.8 mV/F per cell above 77°F (25°C)
+ 3.0 mV/F per cell below 77°F (25°C)
- 3.0 mV/F per cell above 77°F (25°C)
+ 2.8 mV/F per cell below 77°F (25°C)
- 2.8 mV/F per cell above 77°F (25°C)
Battery Series Temperature Compensation
RS02061/0514/CD 11 www.cdtechno.com